GeneralNOTIFIER’s AMPS-24/E is an addressable power supply and battery charger with up to three 24 VDC outputs. It operates in either FlashScan® or CLIP (Classic Loop Interface Protocol) mode with the NFS-3030/NFS2-3030 Fire Alarm Control Panel (FACP). It can also be used as the primary power supply for the NCA-2 Network Control Annunciator.FeaturesAddressable by NFS-3030/NFS2-3030 FACP.Selectable charging current charges 7 AH to 200 AH batteries.Isolated Signaling Line Circuit (SLC) interface.Trouble bus input for use with normally-open dry contacts or open-collector circuit.USB Type B connector for programming installation parameters.Brownout detection.Battery/battery charger supervision.Secondary Power Auxiliary Outputs: 24V @ 0.5A and loss detection and AC loss delay reporting.Mounts in a CAB-4 Series enclosure, EQ Cabinet Series enclosure, BB-25, BB-100, or BB-200 Battery Backbox.